Draft Presidential Regulation Classifies Data Centers by IT Load; Industry Asks 3 MW Threshold Be Reviewed
The draft splits facilities into three classes with PUE, WUE and CUE limits per zone, and the data center operator association IDPRO has publicly asked for the technical basis of the 3 MW boundary to be re-examined.
A draft Presidential Regulation covering submarine cable communication systems and data centers classifies facilities by IT load: Class A at 3 MW and above, Class B between 50 kW and 3 MW, and Class C below 50 kW, each with location rules and efficiency limits that differ by zone, such as maximum PUE of 1.2 and WUE of 2.5 L/kWh for Class C facilities in residential-commercial areas, and 1.4 PUE in special economic zones.
The regulation also mandates energy (PUE), water (WUE) and carbon (CUE) efficiency reporting. Speaking on 18 November, IDPRO chairman Hendra Suryakusuma said the association supports classification as a planning instrument but asked that the 3 MW threshold's technical basis be re-examined, that capacity definitions be clarified between design, installed and operational, that location restrictions not strand investments already under way, and that PUE and WUE indicators be assessed together since lowering power use can raise water consumption.
The rules remain a draft and open for industry input, but if enacted they would require every operator to evidence efficiency metrics continuously, creating sustained demand for metering, logging and audit-ready reporting at facility scale.